Fire Protection System Maintenance Guide for Schools, Offices, Apartments and Data Centres

Fire protection system maintenance is more than replacing expired extinguishers. A multi-storey building can have hundreds to thousands of devices: sprinkler heads, smoke detectors, valves, pumps, pressurisation fans, exit signs. Any device that is not checked on schedule may only be found faulty during a fire.

This guide is compiled by TECO MSC – the maintenance division of TECO Architecture and Construction JSC. It covers the maintenance intervals required by Vietnamese regulations, the fire protection maintenance checklist for each building type, and the order of work.

1. Maintenance intervals under current regulations

From 30 December 2025, maintenance intervals for fire protection equipment and systems follow section 1.5.13 of QCVN 10:2025/BCA, issued with Circular 103/2025/TT-BCA (summary on Thư viện pháp luật, Vietnamese):

System / equipmentMinimum interval
Automatic fire alarm systems, standalone fire alarm devicesOnce a year
Emergency lighting, exit signsOnce a year
Evacuation voice/speaker systemsOnce a year
Outdoor fire water supplyOnce a year
Indoor fire hose (standpipe) systemsOnce a year
Automatic suppression systems (sprinkler, gas, aerosol…)Once a year
Fire extinguishersEvery 6 months

Where the equipment standard or manufacturer requires a shorter interval, the shorter interval applies.

2. Maintenance checklist by system

2.1. Water-based fire fighting

  • Pump set (electric, jockey, diesel): run each pump; check the control panel, pressure switches and auto-start on pressure drop; clean the pump room.
  • Valves and gauges: gate valves, alarm valve assembly, pressure gauges, flow meters, flow switches, valve supervisory switches, floor drain valves, floor pressure-reducing valves.
  • Sprinklers: look for heads painted over, dusty or obstructed; test flow switches at the floor drain valve.
  • Hose cabinets, hydrants, inlet connections: angle valves, hoses, nozzles, fire rules and instructions; flow test at outdoor hydrants.
Pressure gauge on a fire water pipe during fire protection maintenance
Pressure gauge on the fire water line – the first reading to record at every visit.
TECO technician inspecting a sprinkler alarm valve assembly
Inspecting a sprinkler alarm valve assembly.
Fire pump set installed under a staircase
Fire pump set installed under a staircase.
Fire pump and jockey pump next to a rooftop fire water tank
Electric fire pump and jockey pump next to a rooftop fire water tank.
Pressure switches and pressure gauge on a fire pump header
Pressure switches and gauge on the pump header – checking each pump’s cut-in setting.
Inspecting a fire pump control panel during fire protection maintenance
Fire pump control panel opened to check contactors, thermal relays and terminals.
Fire department inlet connection and fire pump house
Fire department inlet and pump house – checking caps, couplings and gaskets.
Checking the hose, nozzle and angle valve in a wall-mounted fire hose cabinet
Checking a wall-mounted hose cabinet: hose, nozzle, angle valve, lock and glass.
Flow test at an outdoor fire hydrant during fire protection maintenance
Flow test at an outdoor fire hydrant.
Maintaining overhead fire water pipes with a fenced-off work zone
Maintaining overhead fire water pipes with the work zone fenced off.

2.2. Fire alarm system

  • Control panel: clean, check settings, standby batteries, each loop connection, fault history.
  • Detectors, call points, sounders/beacons, modules: clean; test smoke detectors with test aerosol and heat detectors with a heat tool; confirm every device signals the panel.
  • Cause and effect: simulate a fire signal and check pressurisation/smoke fans, fire shutters and lift homing (where designed).
Inspecting a fire alarm control panel
Checking the fire alarm control panel – zones, fault indicators, wiring.
Checking a fire alarm and security keypad
Checking the fire alarm / security keypad.
Technician testing a smoke detector with test aerosol during fire protection system maintenance
Testing a smoke detector with test aerosol.
Measuring fire detector base voltage with a multimeter
Measuring detector base voltage with a multimeter.

2.3. Gas, aerosol and early-warning detection

Check the release control panel, release and abort buttons, detectors, batteries and cylinder condition (expiry, mounting). For aspirating smoke detection (ASD/VESDA), check sampling pipes and filters. Never trigger a real discharge during testing – simulate signals only.

Automatic fire extinguisher ball and smoke detector on a ceiling
Automatic fire extinguisher ball and smoke detector on the ceiling.

2.4. Stair pressurisation and smoke extraction

Clean fans and control panels; check auto/manual modes; measure stair pressure differential; inspect smoke extract grilles; test interlock with the fire alarm.

2.5. Exit signs, emergency lights, extinguishers, exit doors

Discharge and recharge exit/emergency light batteries; checklist every extinguisher (pressure, pin, hose, expiry); check exit door hardware and fire shutter rails and motors.

3. Fire protection maintenance by building type

3.1. Schools

  • All items in section 2; prioritise smoke detectors (chalk and playground dust cause false alarms).
  • Manual call points and break-glass units: check for damage by students.
  • Extinguishers: in place, pin intact, pressure OK.
  • Smoke fans in halls, multi-purpose rooms and gyms.
  • Exit signs and emergency lights in corridors and stairs; exit doors not locked during school hours.
  • Schedule: outside school hours, avoiding exam periods.

3.2. Office buildings

  • All items in section 2; stair pressurisation, corridor and basement smoke extraction.
  • After each tenant fit-out: recheck sprinkler and detector positions, obstructions, and signal connections to the panel.
  • Fire doors and stair doors: door closers, self-closing.
  • Schedule: after hours and weekends; notify each floor before cause-and-effect tests.

3.3. Language centres

  • Fire alarm, exit/emergency lights, extinguishers, automatic extinguisher balls, sprinklers (if any).
  • Escape routes: keep desks and bookshelves clear of doors and corridors.
  • Leased space in a building: coordinate with building management when testing signals to the main panel.
  • Multi-site chains: one shared checklist, one schedule for the whole chain, outside class hours.

3.4. Premium apartments

  • Common areas (building management): pump room, fire water tank, basement sprinklers, stair pressurisation, corridor smoke extraction, fire alarm, exit signs, fire doors.
  • Inside apartments: sprinklers, detectors, sounders – book each owner in advance and work floor by floor.
  • After owner renovations: check sprinklers hidden by ceilings or cabinets and detectors that were removed.

3.5. Data centres

  • Gas/aerosol suppression in server, UPS and electrical rooms; ASD/VESDA early-warning detection.
  • Room integrity (doors, wall penetrations) to hold agent concentration.
  • Cause-and-effect tests with release outputs isolated and approved by the operator in advance; no disruption to IT systems.
  • Fire alarm, exit signs, CO2 extinguishers for electrical areas.

4. Order of work

Step 1 – Survey and equipment register

Count and list equipment by system and floor. This is the basis for the quotation and the acceptance checklist.

Step 2 – Work plan

Agree time windows (outside class or office hours, weekends), protected areas and the owner’s contact person.

Step 3 – Inspect and test each device

Follow the checklist in section 2; record pressures, voltages, faulty devices with location and photos.

Step 4 – System cause-and-effect test

Simulate a fire signal and check the chain: sounders – pumps – pressurisation/smoke fans – shutters.

Step 5 – Report and replacement proposal

Hand over the report, the list of faulty devices and replacement proposals. Replacement parts, refurbishment and equipment certification are not included in the maintenance package – they are quoted separately after inspection so the owner can plan the budget.

5. Common faults found during maintenance

  • Pumps left in manual mode after a previous repair and not auto-starting.
  • Weak batteries in fire alarm panels and exit lights that no longer hold the required time.
  • Dusty smoke detectors causing false alarms; users removing detectors instead of cleaning them.
  • Sprinkler heads painted over during ceiling repainting.
  • Extinguishers losing pressure, missing pins or moved from their position.

6. FAQ

How often should a fire protection system be maintained?

Under QCVN 10:2025/BCA: fire alarm, water-based and automatic suppression systems, emergency and exit lights at least once a year; extinguishers at least every six months.

Does the maintenance package include replacing equipment?

No. It covers inspection, cleaning, testing and adjustment. Faulty devices are listed and quoted separately.

Does the building need to shut down?

No. TECO MSC works outside class or office hours and at weekends; occupants are notified before cause-and-effect tests.

Fire protection maintenance enquiries

TECO MSC surveys, builds the equipment register and quotes fire protection maintenance for schools, offices, language centres, apartments, data centres and factories in Ho Chi Minh City and southern provinces.

Hotline: 0911 111 929

See also: Fire protection system maintenance · Routine maintenance · On-demand maintenance